Re: Power consumption

#700
From: John Wright
Date: Sat, 15 Sep 1990 00:25
29 lines
1516 bytes
I must apologize, sometimes I find it faster to dig up answers to
questions that I don't remember the answers to off the mail archives
when I am working away from appropriate manuals. I did that today for
the AGS+ power question and I forwarded a message that had a typo in
it, that particular message had been corrected in a later message
which I did not see in the archive file. Sorry for the confusion, and
many thanks to the dozens of people who have sent me sometimes
humorous replies. ;-)

Here is this question answered by the engineer that does the
specifications/certifications for the power supplies we use:
 ---
 The actual power ratings for the AGS+ product are 7 amps @ 110 VAC
and 3.5 Amps @ 220 VAC.  These are listed in the new installation
guide.

  For UPS information, the AGS+ power supply will hold output for
approximately 20 msec. after power loss at nominal line voltage 
(derate to 6 msec. at low line - 95 VAC-).
  -------
 The 'new installation' guide mentioned is a draft document version  not yet
available.

Again, sorry for the confusion and extra net traffic this has caused.

John Wright
Customer Engineering
cisco Systems, Inc.
-------
Technical Details
Message-ID: <26316@boulder.Colorado.EDU>
Path: arc1-ca.pugleaf.net!utzoo!utgpu!news-server.csri.toronto.edu!cs.utexas.edu!asuvax!ncar!boulder!daemon

Show Full Headers
Complete Article Headers
Path: arc1-ca.pugleaf.net!utzoo!utgpu!news-server.csri.toronto.edu!cs.utexas.edu!asuvax!ncar!boulder!daemon
From: JOHN@heap.cisco.com (John Wright)
Newsgroups: comp.dcom.sys.cisco
Subject: Re: Power consumption
Message-ID: <26316@boulder.Colorado.EDU>
Date: 15 Sep 90 00:25:50 GMT
Sender: daemon@boulder.Colorado.EDU
Lines: 29