Re: Do you ground your Ethernet cable?

#1056
From: jbn
Date: Sun, 18 May 1986 01:53
17 lines
1519 bytes
       The Ethernet I spec called for the outer conductor of the Ethernet
cable to be ungrounded.  Because the connectors are uninsulated, this
created a safety hazard (a short to the braid due to wear between two
rubbing cables, one Ethernet and one power cable would
electrify all the exposed Ethernet connectors but wouldn't blow any breakers) 
and violates the U.S. National Electrical Code.  So the Ethernet II spec 
calls for grounding the Ethernet at exactly one point.
       Back at Ford Aerospace, we grounded our Ethernet with a copper
strap brazed to one of the connector barrels; the copper strap connected
to the building ground system (3/8" x 1.5" copper busbars under the
raised floor tied via heavy copper cable to the grounding rods out back
of the building and cross-connected to power system ground at the wye
of the main transformers; overkill, but a place that builds antennas
takes a dim view of RF noise.)

						John Nagle
Technical Details
Message-ID: <7584@glacier.ARPA>
Path: arc1-ca.pugleaf.net!utzoo!watmath!clyde!burl!ulysses!bellcore!decvax!decwrl!glacier!jbn
References: <261@pedsgo.UUCP>

Show Full Headers
Complete Article Headers
Relay-Version: version B 2.10 5/3/83; site utzoo.UUCP
Path: arc1-ca.pugleaf.net!utzoo!watmath!clyde!burl!ulysses!bellcore!decvax!decwrl!glacier!jbn
From: jbn@glacier.UUCP
Newsgroups: net.lan,net.dcom
Subject: Re: Do you ground your Ethernet cable?
Message-ID: <7584@glacier.ARPA>
Date: Sat, 17-May-86 21:53:54 EDT
Article-I.D.: glacier.7584
Posted: Sat May 17 21:53:54 1986
Date-Received: Fri, 23-May-86 07:52:39 EDT
References: <261@pedsgo.UUCP>
Distribution: net
Organization: Stanford University, IC Laboratory
Lines: 17
Summary: Grounding of Ethernets