The Ethernet I spec called for the outer conductor of the Ethernet
cable to be ungrounded. Because the connectors are uninsulated, this
created a safety hazard (a short to the braid due to wear between two
rubbing cables, one Ethernet and one power cable would
electrify all the exposed Ethernet connectors but wouldn't blow any breakers)
and violates the U.S. National Electrical Code. So the Ethernet II spec
calls for grounding the Ethernet at exactly one point.
Back at Ford Aerospace, we grounded our Ethernet with a copper
strap brazed to one of the connector barrels; the copper strap connected
to the building ground system (3/8" x 1.5" copper busbars under the
raised floor tied via heavy copper cable to the grounding rods out back
of the building and cross-connected to power system ground at the wye
of the main transformers; overkill, but a place that builds antennas
takes a dim view of RF noise.)
John Nagle
Technical Details
Message-ID:
<7584@glacier.ARPA>Path:
arc1-ca.pugleaf.net!utzoo!watmath!clyde!burl!ulysses!bellcore!decvax!decwrl!glacier!jbnReferences:
<261@pedsgo.UUCP>Show Full Headers
Complete Article Headers
Relay-Version: version B 2.10 5/3/83; site utzoo.UUCP Path: arc1-ca.pugleaf.net!utzoo!watmath!clyde!burl!ulysses!bellcore!decvax!decwrl!glacier!jbn From: jbn@glacier.UUCP Newsgroups: net.lan,net.dcom Subject: Re: Do you ground your Ethernet cable? Message-ID: <7584@glacier.ARPA> Date: Sat, 17-May-86 21:53:54 EDT Article-I.D.: glacier.7584 Posted: Sat May 17 21:53:54 1986 Date-Received: Fri, 23-May-86 07:52:39 EDT References: <261@pedsgo.UUCP> Distribution: net Organization: Stanford University, IC Laboratory Lines: 17 Summary: Grounding of Ethernets