Article #289Re: Two phases to house - loss of neutral
From: Sylvia Else
Date: Tue, 24 Nov 2009 01:24
Date: Tue, 24 Nov 2009 01:24
53 lines
3559 bytes
3559 bytes
Phil Allison wrote: > "Stupider than Anyone Else" > >> I have to phases of power supply to my house - so three power lines, two >> phases plus neutral. >> >> I've on occasion wondered what would happen if we lost the neutral line. >> It seems to me that we'd then have the voltage between the two phases >> across two sets of appliances, one set attached to one phase, and the >> other set attached to the other phase, with the two sets in series as a >> result of their common connection to the neutral wire. Since the two sets >> are unlikely to represent equal loads, the net result would be a large >> overvoltage on one set of appliances. >> >> My electrician says it's not an issue, but I can't see why. > > > ** Loss of the neutral conductor in a 3 phase ( or 2 phase) AC supply system > can easily be a DISASTROUS event. > > For example: > > In the live entertainment productions - high powered lighting and sound > systems operate from 3 phase outlets via a hefty 5 pin plug and socket. If, > due to wear and tear or damage to the plug or socket, one of the phases > drops out - that is an annoyance but not a disaster. > > However, if the pin carrying the neutral fails to connect or as is often the > case *disconnects* during a show because of overheating - ALL HELL > BREAKS LOOSE !! > > Typically, some of the lamps will glow very brightly for a second or two and > fail, then other previously dim lamps will follow suit. The AC fuses in > amplifiers will pop instantly and some equipment will be seriously damaged > when the PSU sections are destroyed. It all happens in a few seconds, while > the operators stand there with their mouths open !!! > > The MEN system: > > In Australia, AC power delivery uses a system called " Multiple Earth > Neutral " - which requires that the neutral conductors in a premises be > connected to the plumbing system at the distribution board (ie power box). > It also requires that an earth stake be installed for the same purpose, but > some older premises may not have this. If as you say, neutral has to be tied to Earth at the premises, then I can indeed see that the situation might not be so bad. On the face of it, having significant current flowing from neutral to Earth would have to indicate a fault. It would be nice for the breakers to trip in such a situation, but I can't see that they will. Sylvia.
Technical Details
Message-ID:
<00870716$0$26916$c3e8da3@news.astraweb.com>Path:
arc1-ca.pugleaf.net!g2news1.google.com!news2.google.com!news.glorb.com!news2.glorb.com!news.astraweb.com!border1.newsrouter.astraweb.com!not-for-mailReferences:
<0083b31e$0$1587$c3e8da3@news.astraweb.com> <7n0peqF3jloctU1@mid.individual.net>Show Full Headers
Complete Article Headers
X-Google-Thread: a5a6238865,dcb8eebd9233b785 X-Google-Attributes: gida5a6238865,public,usenet X-Google-NewGroupId: yes X-Google-Language: ENGLISH,ASCII-7-bit Path: arc1-ca.pugleaf.net!g2news1.google.com!news2.google.com!news.glorb.com!news2.glorb.com!news.astraweb.com!border1.newsrouter.astraweb.com!not-for-mail Date: Tue, 24 Nov 2009 12:24:40 +1100 From: Sylvia Else <sylvia@not.at.this.address> User-Agent: Thunderbird 2.0.0.23 (Windows/20090812) MIME-Version: 1.0 Newsgroups: sci.electronics.repair,aus.electronics Subject: Re: Two phases to house - loss of neutral References: <0083b31e$0$1587$c3e8da3@news.astraweb.com> <7n0peqF3jloctU1@mid.individual.net> In-Reply-To: <7n0peqF3jloctU1@mid.individual.net> Content-Type: text/plain; charset=ISO-8859-1; format=flowed Content-Transfer-Encoding: 7bit Lines: 53 Message-ID: <00870716$0$26916$c3e8da3@news.astraweb.com> Organization: Unlimited download news at news.astraweb.com NNTP-Posting-Host: ad01d8be.news.astraweb.com X-Trace: DXC=R`:R7d4Ai59IHnC;ELbe^;L?0kYOcDh@:EE63Zc8>Ue7CLD<5=23j?35;;M`E3\ML<0RAGG4SR[>02^PSCSQlYZ<0D9am3HTln1