dave@imax.imax.com (Dave Martindale) writes:
> I just bought an old Sola CVS-series constant-voltage transformer.
> It works as advertised - as the input voltage is varied from 95 to 130 V,
> the output voltage changes about 2% (or +-1%, if you prefer to think of
> it that way).
>
> Of course, no documentation of any kind came with it. So I have a couple
> of questions I hope someone can answer:
>
> 1. How does it WORK? I can't explain how it does its voltage regulation
> trick with just a transformer and a capacitor. None of the reference
> books I have around discuss it either.
>
> I have noticed that if you bring the input voltage up from zero,
> the device acts at first like a normal isolation transformer - output
> voltage varies with input voltage, and in addition the thing is
> absolutely quiet. Then, at somewhat below half of nominal input
> voltage, the transformer suddenly starts buzzing, and the output
> voltage jumps to almost the regulated range - it's almost as if
> an oscillator was starting up. The phase is even a bit unsteady
> for a few cycles - you can hear the pitch "bounce" as it starts up.
>
> 2. The label says that the transformer is "harmonic neutralized". What
> would the output waveform look like without this?
>
> 3. What sort of winding temperature would the transformer be designed for?
> I've had it running at a little under 1/2 rated load for a few hours,
> with the input voltage at the lower end of the regulation range,
> and the temperature inside the core is about 70 degrees Celcius.
> This seems a bit high to me for only half load.
>
> Dave
Its a ferro-resonant transformer; there's a tuned circuit in there
resonant at 60 HZ. The amplitude of response is limited by saturation
of the magnetic core; since the core is constantly switching from
+ve to -ve saturation on each cycle, the flux change is about constant
and so the secondary voltage remains about the same. This explains your
other observations; you see it behave as a "linear" transformer
until the applied voltage is high enough to saturate the core. It
buzzes, because of a magnetostricive effect ( also if any of the
laminations are loose) due to the saturated field switching on each
line cycle. It gets hot, because of higher hysteresis losses in the
core - don't worry, they are designed for this and will run for years
at a high temperature.
Not sure exactly what the output waveform would look like but I
expect it would be almost square or possibly a heavily clipped
triangular wave; the compensated unit probably has enough filtering
on the output to bring the waveform to an approximate sine wave.
Useful units, these; for example, people who run enlargers
like them because it makes the line voltage to the enlarger independant
of line voltage fluctuations. Not terribly energy-efficient, of
course, as you can guess; but before the advent of the $10 switch
mode supply, this was the only way to go.
Bill
bills@inqmind.bison.mb.ca
The Inquiring Mind BBS, Winnipeg, Manitoba 204 488-1607
Technical Details
Message-ID:
<4yN9TB3w165w@inqmind.bison.mb.ca>Path:
arc1-ca.pugleaf.net!sparky!uunet!newsflash.concordia.ca!mizar.cc.umanitoba.ca!ccu.umanitoba.ca!bison!sys6626!inqmind!billsReferences:
<1992Nov15.031727.25053@imax.imax.com>Show Full Headers
Complete Article Headers
Path: arc1-ca.pugleaf.net!sparky!uunet!newsflash.concordia.ca!mizar.cc.umanitoba.ca!ccu.umanitoba.ca!bison!sys6626!inqmind!bills From: bills@inqmind.bison.mb.ca (Bill Shymanski) Newsgroups: sci.electronics Subject: Re: How do constant voltage (ferroresonant) transformers work? Message-ID: <4yN9TB3w165w@inqmind.bison.mb.ca> Date: Sat, 14 Nov 92 11:05:02 CST References: <1992Nov15.031727.25053@imax.imax.com> Organization: The Inquiring Mind BBS 1 204 488-1607 Lines: 62