Article View: sci.electronics
Article #16694Re: NEED SOLENOID ACTUATED WATER VALVE.....
From: jb
Date: Fri, 08 Jan 1993 01:44
Date: Fri, 08 Jan 1993 01:44
117 lines
5000 bytes
5000 bytes
philb@techbook.com (Phil Biehl) said ...
> Hi. In examining my hydronic (hot water basboard) furnace, I find that
> it is divided up into three zones. What I'd like to do is put in
> electrically operated valves that controlled via a microcontroller and
> three separate thermostats, one for each zone. I need to find a source
> for these valves that will fit 7/8" copper piping. 12 Volt coils would
> be nice but not absolutely necessary.
The following is provided as technical info only, other manufacturers
exist. Prices are provided as reference only, etc...
\begin{quote}
HVAC Controls - Hydronic Controls.
1. "Honeywell" ZONE VALVES
for Controlling the Flow of Hot and Cold Water.
Features:
* Long Life, Synchronous Motor - Virtually noiseless operation, and
a smooth-opening feature that prevents water hammer. Motor can be
easily replaced by removing one screw without having to drain
system.
* Switch up to 5 valves with one 40VA transformer - Save on
multiple transformer installations. Each V8043 is rated at
7.7VA(X5+38.5VA).
* Manual opener with automatic recycle - In case of power failure
valve can be opened manually for emergency heat. Valve will return
to "Auto" position when power is restored.
* Forged brass body - because the rubber ball seat rotates out of the
way, sweat fittings is accomplished without disassembling the valve.
This makes for a very durable body.
* Three O-Ring seal - Chance of seal leakage is practically
nonexistant. No other zone valve provides the degree of protection
against leaks.
Valves consist of an actuator motor and valve assembly. Compact
construction allows this valve to fit most anywhere including under
baseboards. Integral auxiliary end switch permits the sequencing of
auxiliary equipment. Patented rotating rubber ball seat never seats
twice in same position which allows for a long life seal.
Specifications: End switch - 4.4 amps (26.4 amps inrush) Pilot duty -
50VA@24V. 18" wire leads. Current draw - 3.2 amps.
MFG. Part #: V8043E1004
Series: E
De-energized Position: Normally Closed
Pipe Connection: 1/2" Sweat
Control Circuit: 24/50-60hz
Dealer Price: (1) $59.27, (3) $56.31
MFG. Part #: V8043E1012
Series: E
De-energized Position: Normally Closed
Pipe Connection: 3/4" Sweat
Control Circuit: 24/50-60hz
Dealer Price: (1) $63.32, (3) $56.99
MFG. Part #: V8043E1020
Series: E
De-energized Position: Normally Closed
Pipe Connection: 1" Sweat
Control Circuit: 24/50-60hz
Dealer Price: (1) $71.74, (3) $64.57
2. White Rodgers Hydronic Zone Controls
* 2-Wire or 2-way compact zone valves for maximum system pressure of
150 PSI
* For 24 VAC baseboard units, fan coils, convectors, etc.
* Controls feature an adjustable flow valve and a unique spanner nut
construction which makes them ideal for heating and cooling systems
* Design allows power head to be assembled directly to valve body with
no "swing distances", making installation and servicing easier
* 2-wire thermostat controls a non-synchronous torque motor to open
valve
* valves have 3/4" I.D. sweat fitting
* L36-637 valve includes an auxiliary switch which provides a low
voltage (.35A at 24V) circuit to control burner/chiller, and/or
circulator
* 40 degree F to 250 degree F water temperatures
* 18" leads on L36-636, push on connectors on L36-637
* Shipping weight 2.5 lbs.
White Rogers part #: 13A01-102
Time Cycle: Open 30 Sec., Close 20 Sec.
Friction DV Factor: 6.0
Equivalent Ft. of Tubing: 22
Order Stock #: L36-636
Dealer Price: $55.58
White Rogers part #: 13A02-102
Time Cycle: Open 30 Sec., Close 20 Sec.
Friction DV Factor: 6.0
Equivalent Ft. of Tubing: 22
Order Stock #: L36-637
Dealer Price: $64.32
\end{quote}
from pages 255-256, catalog 173,
"Johnstone Supply Wholesale Net Price Book, Spring 1992"
Johnstone Supply, Inc.
PO Box 3010
Portland, Or 97208
(two offices in NC, no other offices listed)
It appears that hydronic systems are sensitive to pressure drops. I
know that some designs have no circulator pumps.
Caution: Copper pipe is sold by both inside (ID) and outside diameter
(OD) measurements.
My dad used to service forced-air oil systems.
Jeff Bartlett
Technical Details
Message-ID:
<1993Jan8.014417.10590@rti.rti.org>Path:
arc1-ca.pugleaf.net!sparky!uunet!spool.mu.edu!sdd.hp.com!swrinde!gatech!concert!rti!jbReferences:
<C0Eoqw.5Dq@techbook.com>Show Full Headers
Complete Article Headers
Newsgroups: sci.electronics Path: arc1-ca.pugleaf.net!sparky!uunet!spool.mu.edu!sdd.hp.com!swrinde!gatech!concert!rti!jb From: jb@rti.rti.org Subject: Re: NEED SOLENOID ACTUATED WATER VALVE..... Message-ID: <1993Jan8.014417.10590@rti.rti.org> Keywords: HVAC Controls Hydronic Controls. Organization: Research Triangle Institute, RTP, NC References: <C0Eoqw.5Dq@techbook.com> Distribution: usa Date: Fri, 8 Jan 93 01:44:17 GMT Lines: 117