Yes, there is a convenient way.  You just run a normal watthour
meter with the "voltage" coil 90 degrees out of its normal phase.
This integrates reactive power just as the normal connection
integrates real power.  Read both meters and a simple formula
gives you your average power factor.

At an auto plant where I worked, the real power was read automatically
every 15 minutes by a recorder on the meters, and the reactive power
was read by the meter reader when he came to eyeball-check the real
power meters and change the recording medium.  I assume different
utilities track power factor differently, depending on their regulatory
agencies.

===========================================================================
  "I've got code in my node."	| UUCP:  ...!ihnp4!itivax!node!michael
				| AUDIO: (313) 973-8787
	Michael McClary		| SNAIL: 2091 Chalmers, Ann Arbor MI 48104
---------------------------------------------------------------------------
Above opinions are the official position of McClary Associates.  Customers
may have opinions of their own, which are given all the attention paid for.
===========================================================================
Technical Details
Message-ID: <1229@m-net.UUCP>
Path: arc1-ca.pugleaf.net!utzoo!mnetor!seismo!rutgers!sri-spam!ames!ptsfa!well!msudoc!umich!itivax!m-net!michael
References: <923@mhuxh.UUCP> <1715@kitty.UUCP> <555@neoucom.UUCP>

Show Full Headers
Complete Article Headers
Relay-Version: version B 2.10 5/3/83; site utzoo.UUCP
Path: arc1-ca.pugleaf.net!utzoo!mnetor!seismo!rutgers!sri-spam!ames!ptsfa!well!msudoc!umich!itivax!m-net!michael
From: michael@m-net.UUCP (Michael McClary)
Newsgroups: sci.electronics
Subject: Re: Domestic KiloWatt Hour Meters
Message-ID: <1229@m-net.UUCP>
Date: Mon, 27-Apr-87 00:02:49 EDT
Article-I.D.: m-net.1229
Posted: Mon Apr 27 00:02:49 1987
Date-Received: Sat, 2-May-87 09:36:19 EDT
References: <923@mhuxh.UUCP> <1715@kitty.UUCP> <555@neoucom.UUCP>
Reply-To: michael@m-net.UUCP (Michael McClary)
Organization: M-NET, Ann Arbor, MI
Lines: 30
Keywords: meters,power,watthour