From: Larry Lippman
Date: Sat, 15 Apr 1989 20:10
Date: Sat, 15 Apr 1989 20:10
45 lines
3007 bytes
3007 bytes
In article <880004@hpmtlx.HP.COM>, dc@hpmtlx.HP.COM ($Dave Crook) writes:
> In many cases, especially in residential lines, the losses in the power
> lines themselves are far greater than the losses in the transformers.
This is true. Efficient power distribution has many trade-offs.
There is a significant trend toward higher distribution voltages to
minimize the effects of I^2R losses. Many electric utilities have switched
from 4160 volts to 13.2 kV for distribution in residential areas. For
commercial distribution 34.5 kV has also become common.
However, a negative effect with higher voltages is increased losses
due to capacitance, corona and - especially - insulator leakage losses
during wet weather.
> If the transformer does not have large heat radiating tubes or fins, the
> chances are that it is quite efficient. Since all losses are converted
> to heat, the heat dissipating sinks are a directly measure of the losses
> the transformer was designed to dissipate at maximum load.
While you have a point, this is not necessarily true. With advances
in high-voltage insulating materials, many "intermediate"-sized transformers
contain no oil or gas (like SF6), but are air-cooled through convection,
and consequently have no fins as part of their design. Air-cooled
transformers still get hot, though.
> Many "transformers" are actually transformer regulators. Inside the
> "transformer" is an electronic voltage detection circuit which controls
> the voltage ratio. Under heavy loads the ratio increases which compensates
> for significant voltage and power loss in the power lines feeding the
> transformer.
There are high-voltage power line voltage regulators of two types:
(1) buck-boost autotransformer; and (2) a true transformer with a tap
changer. However, these regulating devices are used more infrequently
than you suggest. Large transformers of the multi-MVA variety that
distribute voltages of 34.5 kV and above usually have taps that are
changed either manually (through a switch on the transformer), or
through a remote telemetering circuit by a human operator. Large
transformers that employ automatic tap changing to achieve automatic
regulation are not very common.
<> Larry Lippman @ Recognition Research Corp. - Uniquex Corp. - Viatran Corp.
<> UUCP: {allegra|ames|boulder|decvax|rutgers|watmath}!sunybcs!kitty!larry
<> VOICE: 716/688-1231, 716/773-1700 {att|hplabs|utzoo}!/
<> FAX: 716/741-9635, 716/773-2488 "Have you hugged your cat today?"
Technical Details
Message-ID:
<3094@kitty.UUCP>Path:
arc1-ca.pugleaf.net!utzoo!utgpu!jarvis.csri.toronto.edu!mailrus!tut.cis.ohio-state.edu!rutgers!sunybcs!kitty!larryReferences:
<731@hutto.UUCP> <880004@hpmtlx.HP.COM>Show Full Headers
Complete Article Headers
Path: arc1-ca.pugleaf.net!utzoo!utgpu!jarvis.csri.toronto.edu!mailrus!tut.cis.ohio-state.edu!rutgers!sunybcs!kitty!larry From: larry@kitty.UUCP (Larry Lippman) Newsgroups: sci.electronics Subject: Re: How efficient are transformers? Summary: Power line regulation... Message-ID: <3094@kitty.UUCP> Date: 15 Apr 89 20:10:48 GMT References: <731@hutto.UUCP> <880004@hpmtlx.HP.COM> Organization: Recognition Research Corp., Clarence, NY Lines: 45