Re: APC SmartUPS problem

#235
From: Alex Threlfall
Date: Tue, 08 Jun 2004 10:46
30 lines
2294 bytes
In article <jfq9c01kogmrku8hedjt5hrb4k4e8ea1pj@4ax.com>, 
paul@hopwood.org.uk says...
> 
> I'm running a PC off a APC SmartUPS 420.  It passes self-test and,
> after four hours or so, the PowerChute software reports the battery
> capacity to be at 100% with 6 minutes of runtime remaining.  The load
> looks fine, with one PC fitted with a 400W PSU drawing around 35%-40%
> of capacity, depending on what it's doing at the time.
> 
> However, if I pull the AC supply the UPS and the attached server die
> immediately.  If I run PowerChute after reconnecting power and
> bringing it back up it reports the battery is discharged and only has
> about 20% charge with less than a minute run time.
> 
> My gut feeling is the battery is shafted (if so any recommendations
> where I can buy a replacement without paying APC reseller prices?) but
> I'm not entirely convinced as it behaves as I'd expect a good one to,
> shows normal charging patterns and passes the UPS self-test.  Anyone
> able to shed any light on it?
> 
> 
RS Components, the batteries are probably shafted as you say. I fixed 
mine by getting new batteries for it, and it's been running for the last 
year just fine ;)
-- 
  Alex Threlfall
Cyberprog New Media
 www.cyberprog.net
tel - 0870 446 0789
fax - 0870 446 1789
Technical Details
Message-ID: <MPG.1b2f1208d82dee6a989728@news-text.blueyonder.co.uk>
Path: arc1-ca.pugleaf.net!g2news1.google.com!news1.google.com!news.glorb.com!fr.ip.ndsoftware.net!proxad.net!proxad.net!news-hub.cableinet.net!blueyonder!news-text.cableinet.net!53ab2750!not-for-mail
References: <jfq9c01kogmrku8hedjt5hrb4k4e8ea1pj@4ax.com>

Show Full Headers
Complete Article Headers
X-Google-Language: ENGLISH,ASCII-7-bit
X-Google-Thread: 1063f0,32a19d7fea2ee17a
X-Google-Thread: 1036bc,c36563a0f1637fe5
X-Google-Attributes: gid1063f0,gid1036bc,public
Path: arc1-ca.pugleaf.net!g2news1.google.com!news1.google.com!news.glorb.com!fr.ip.ndsoftware.net!proxad.net!proxad.net!news-hub.cableinet.net!blueyonder!news-text.cableinet.net!53ab2750!not-for-mail
From: Alex Threlfall <alex@nospam.cyberprog.net>
Newsgroups: uk.comp.homebuilt,demon.tech.pc
Subject: Re: APC SmartUPS problem
Message-ID: <MPG.1b2f1208d82dee6a989728@news-text.blueyonder.co.uk>
References: <jfq9c01kogmrku8hedjt5hrb4k4e8ea1pj@4ax.com>
Organization: Cyberprog New Media
Reply-To: alex@cyberprog.net
X-Newsreader: MicroPlanet Gravity v2.50
Lines: 30
Date: Tue, 08 Jun 2004 10:46:30 GMT
NNTP-Posting-Host: 82.32.59.119
X-Complaints-To: abuse@blueyonder.co.uk
X-Trace: news-text.cableinet.net 1086691590 82.32.59.119 (Tue, 08 Jun 2004 11:46:30 BST)
NNTP-Posting-Date: Tue, 08 Jun 2004 11:46:30 BST